PDIMU   POWER DISTRIBUTION 
 ISOLATION & MANAGEMENT UNIT

POWERTRONIX PDIMUs offer the isolation of our MIU, the voltage regulation and noise suppression of our PLC, and the AC power distribution capabilities of our PDU. In addition, they include new features, such as intelligent soft start with sequential load distribution, voltage selectable input - ranging from 100 Volt to 240 Volt (see specifications below), ultra low output impedance (<0.5ohm.), and an emergency circuit breaker. The featured unit is of industrial grade, but we also offer medical grade PDIMUs (with UL 2601 approval, and IEC 601.1, VDE 750 Part 1, and CSA 22.2 No. 601.1-M90 compliance.)

A variety of voltage ratings, enclosures, connectors and receptacles are available.

APPLICATIONS
POWERTRONIX PDIMUs are used with semi-conductor manufacturing and automatic test equipment, robotics, main frame computer systems, medical imaging, and medical lasers.

Picture

REAR PANEL

Picture

INTERNAL CONFIGURATION OF COMPONENT PARTS

Picture

SPECIFICATIONS

. Input Voltage:
. Frequency:
. Isolation:
. Output Voltage:
. Power Range:
. Ambient Temperature
. Efficiency:

110/115/120/200/208/220/230/240V
47 Hz - 63 Hz
4,000 VRMS
120/240 V
720 VA - 4,800 VA
0 °- 40°C
97%

SAFETY APPROVALS

BUILT TO

. UL 506
. UL 1950
. CSA 22.2, No. 66
. CE Marking

. IEC 950
. IEC 1000-4-5
. IEC 1000-4-11

Model
Number

Power
(VA)

Dimensions LxWxH

Weight
(lbs)

PDMIU 0720

720

8.5" x 11" x 3.5"

20

PDMIU 1200

1200

17" x 14" x 3.5"

28

PDIMU 2400

2400

17" x 14" x 5.2"

40

PDIMU 3600

3600

19" x 14" x 5.2"

60

PDMIU 4800

4800

19" x 14" x 7.0"

78

Picture

A EMERGENCY CIRCUIT BREAKER
A breaker that will cut power to the PDIMU and its output in the event of an emergency. As a safety precaution, the unit can only be restarted by powering the system off (from the AC mains) and re-booting, once this breaker has been tripped.

B CIRCUIT BREAKER
A 2-pole, current limiting, rocker type on/off breaker for standard operation.

C INPUT PROTECTION
In order to assure the safety of the PDIMU and its load, this component protects the input from short circuit conditions on the output. In addition, it provides protection from ground fault interruptions that can lead to dangerous line-to-ground and shock hazard currents, as well as electrical fires.

D SOFT START
A standard feature in all POWERTRONIX PDIMUs with a power rating greater than 2 kVA. It facilitates a smooth start up, by restraining damaging in-rush currents.

* ISOLATION TRANSFORMER/FILTER
This is the core of the POWERTRONIX PDIMU, and it incorporates components E and F that provide over-temperature protection and low frequency noise suppression, respectively. Components E and F are integrated within a low impedance, highly insulated and well-shielded POWERTRONIX Toroidal Transformer, which itself eliminates ground-loop problems, insulates connected equipment against potentially harmful leakage currents, and provides extended brownout range.

E THERMAL PROTECTION
A resetable thermal switch that automatically shuts off the power to the unit and connected equipment at a set temperature. The shut off temperature is based on the class of insulation in the toroidal transformer, as well as the application for which the unit is intended. Typically, the switch will trip at 110°C, and allow for restart once the unit has cooled down to approximately 70°C.

F NON-LINEAR FILTER
This element prevents low frequency noise (<3 kHz) from reaching the sensitive load.

G HIGH FREQUENCY SUPPRESSION
This module limits EMI and RFI, in addition to other high frequency noise
(2.5 kHz to 300MHz), from reaching the sensitive load.

H SEQUENTIAL LOAD DISTRIBUTION
This feature limits the amount of strain placed on the PDIMU at start up, and extends added protection to connected equipment. Output receptacles are activated sequentially. Each output (following the first) is restrained until the current on the previous one has gone beyond its peak value and has decayed to a steady state value.

All data are typical values and subject to change without prior notice.

Medical grade power distribution, isolation and management units are also available for applications that require UL 2601 approval,IEC 601.1 compliance, and a leakage current that is less than 100 µA.

Custom designed Power Distribution, Isolation and Management
Units are also available!

Powertronix . 1120 Chess Drive, Foster City, CA 94404
Tel: (650) 345-6800 . Fax: (650) 345-7240